8.2

Activating additional functions in the signal flow

The following parameters serve to activate further functions in the main signal flow that are first

deactivated by default:

Parameter

Name

Info

Application paramete

rs (exten

de

d)

C00598/1

Resp. to open circuit AIN1

Response to open circuit at the analog input when

being configured as 4 ... 20 mA current loop.

Lenze setting: "TroubleQuickStop". The drive is braked

to standstill within the deceleration time

parameterised for quick stop independently of the

defined setpoint and can be kept there.

C00950/1

Activation of signal interpolation

Signal interpolation and monitoring

(see reference manual; FB L_Interpolator_1)

C00950/2

Activation of signal monitoring

C00951

L_Interpolator_1:

No. of interpolation steps

C00952

L_Interpolator_1:

Limit value - error cycles

C00696

L_OffsetGainP_1: Offset

Offset and gain

(see reference manual; FB L_OffsetGainP_1)

C00670

L_OffsetGainP_1: Gain

C00635

L_NSet_1: nMaxLimit

Speed limit values ( 59)

C00636

L_NSet_1: nMinLimit

C0632/1...3

L_NSet_1: Blocking speed 1 ... 3 max

Speed blocking zones ( 60)

C0633/1...3

L_NSet_1: Blocking speed 1 ... 3 min

C00134

Ramp smoothing main setpoint

Ramp smoothing ( 61)

C00182

S-ramp time PT1

C02830

DIx: Debounce time

Debounce and delay times for digital inputs and

outputs

C00423

DOx: Delay times

C00472/3

LS_ParFree_a: Value 3

Torque limitation in motor mode and in generator

mode. Lenze setting: 100 %

• The drive cannot output a higher torque in

motor/generator mode than set here.

• If V/f characteristic control (VFCplus) is selected,

limitation is indirectly performed via the Imax

controller.

C00472/4

LS_ParFree_a: Value 4