5

Before commissioning

5.4

Frequently used device commands

24

Lenze · 8400 StateLine · Operating instructions · from Firmware V06.00 · DMS 1.2 EN · 12/2012 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

5.4

Frequently used device commands

The device commands available in the subcodes of C00002 serve, among other things, to directly

control the controller, to organise parameter sets, and to call diagnostic services.
Regarding the execution of the device commands, a distinction is drawn between:

• Device commands which have an immediate effect on control (e.g. "Delete logbook")

• After being called in C00002/x, these device commands provide static status information

("On" or "Off").

• Device commands with longer execution duration (several seconds)

• After being called in C00002/x, these device commands provide dynamic status information

("work in progress 20 %"  "work in progress 40 %", etc.).

• The execution of the device command has not finished successfully until the "Off / ready"

status information is provided in C00002/x.

• In the event of an error, the "Action cancelled" status information is provided in C00002/x

. In

this case, further details can be obtained from the status of the device command executed

last which is displayed in C00003.

C00002/1

C00002/11

Parameter

Name

Controller inhibit required

Status information

Co

mm

an

ds

C00002/1

Load Lenze setting

dynamic

C00002/11

Save all parameter sets

dynamic

C00002/19

Reset error

static

C00002/21

Delete logbook

static

C00003

Status of the last device command

Load Lenze setting
This device command serves to reset all parameter settings in the device to the Lenze setting in order to keep a

defined device configuration.

Note: All parameter changes which have been carried out after the last time the parameter set was saved will be

lost!

• Only possible when the controller is inhibited.

Selection list

(Lenze setting printed in bold)

Info

0 Off / ready
1 On / start

Reset all parameters to the Lenze setting

(Restore delivery status)

Save all parameter sets
Note:
During the storage process:

• Do not switch off the supply voltage!

• Do not remove the memory module from the device!

Selection list

(Lenze setting printed in bold)

Info

0 Off / ready
1 On / start

Save parameter settings in the memory module of the

controller safe against mains failure