Lenze · 8400 StateLine · Operating instructions · from Firmware V06.00 · DMS 1.2 EN · 12/2012 · TD05

31

6

Commissioning

6.2

Quick commissioning with the keypad

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Select speed setpoint
In case of terminal control in the preset control mode "Terminals 0":

• In the Lenze setting, the main speed setpoint is selected via the analog terminal X3/A1U (e.g. via

a setpoint potentiometer).

• Scaling: 10 V ≡ 100 % reference speed (C00011) ≡ 1500 rpm

(applies to 4-pole asynchronous motors)

In case of keypad control:

1. Navigate to parameter C00728/3.
2. Set the desired setpoint speed in [%] with regard to the reference speed set in C00011 (CCW

rotation: -199.99 % .... 0, CW rotation: 0 ... +199.99 %).

In order to prevent jumps, the main speed setpoint is led via a ramp generator with linear ramps:

[6-2]

Speed profile with preset ramp generator with linear ramps

Using fixed setpoints
Alternatively to the setpoint selection via the analog input or C00728/3. "fixed setpoints" can also

be activated according to the following truth table:

• Fixed setpoints refer to the reference speed set in C00011.

reference speed (1500 rpm)

acceleration time

deceleration time

Q



W



V

V

n

p

o

Terminal control

Keypad control

Speed selection

DI1

DI2

C00727/5

C00727/4

LOW

LOW

0

0

The setpoint speed is selected via the analog input 1 or with

keypad control via C00728/3.

HIGH

LOW

1

0

Setpoint speed = fixed setpoint 1 (C00039/1: 40 %)

LOW

HIGH

0

1

Setpoint speed = fixed setpoint 2 (C00039/2: 40 %)

HIGH

HIGH

1

1

Setpoint speed = fixed setpoint 3 (C00039/3: 40 %)