Diagnostics & troubleshooting

7.5

Error messages

50

Lenze · 8400 StateLine · Operating instructions · from Firmware V06.00 · DMS 1.2 EN · 12/2012 · TD05

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

OC2: Power section - earth fault

The device has recognised an earth fault at

one of the motor phases. To protect the

device electronics, the inverter control is

switched off.

• Mostly, incorrectly executed motor

connections are the cause.

• If motor filter, motor cable length, and

cable type (shielding capacity) are

dimensioned incorrectly, this error

message may occur due to leakage

currents to PE.

• If motor filters with additional

terminals for +UG and –UG and devices

greater or equal 3 kW are used, the

earth fault detection may be triggered

due to leakage currents to +UG and –

UG.

• A cause can also be the use of shielded

motor cables longer than 50 m.

• Check motor connections and the

corresponding plug connector on the

device.

• Use motor filters, cable lengths, and

cable types recommended by Lenze.

• If motor filters with additional

terminals for +UG and –UG and devices

greater or equal 3 kW are used:

Deactivate earth fault detection during

operation by setting the filter time

(C01770) to 250 ms.

• If shielded motor cables longer than

50 m are used: Increase the filter time

for earth fault detection during

operation (C01770).

OC5: Ixt overload

The Ixt overload check has tripped.

• Operating threshold = 100 % Ixt

(adjustable in C00123)

Possible causes:

• Wrong dimensioning of the device with

regard to its motor load.

• Load cycles are not complied with.

• Check and, if required, correct

dimensioning of the device and the

motor load with regard to technical

data.

• Reduce motor load cycles (observe load

cycles according to documentation).

OC6: I2xt motor overload

Thermal overload of the motor.

• Observe load requirements.

• Correct dimensioning if necessary.

• In case of VFCplus operation: Check

Vmin boost (C00016).

OC7: Motor overcurrent

The maximum current monitoring has

tripped.

• The instantaneous value of the motor

current has exceeded the limit value

set in C00939.

Check and, if required, correct

dimensioning of the load with regard to

the installed device power.

OC10: Max. current reached

The device displays that the maximum

current has been reached.

• Check and, if required, correct

dimensioning of the load with regard

to the installed device power.

• Check the maximum current settings

in C00022 (Imax in motor mode) and

C00023 (Imax in generator mode).

OC11: Active clamp operation

The device indicates that the "CLAMP"

overcurrent limitation has been activated.

• A permanent clamp operation causes

an overload disconnection.

Reduce setpoint generation dynamics or

motor load.

OC12: I2xt overload - brake resistor

Too frequent and too long braking

processes.

Check drive dimensioning.

OC13: Max. current for Fch exceeded

The device has detected a motor current

which exceeds the maximum current limit

at permanent switching frequency of the

inverter.

• If a permanent switching frequency

inverter is set, a certain limit arises for

the maximum current, depending on

the setting. If this current limit is

exceeded due to a load impulse or

overload, an error message is

displayed.

• Observe the maximum current setting

depending on the set switching

frequency of the inverter.

• Reduce the required load or setting of

the dynamic switching frequency if

necessary.

Error message

Cause

Remedies