Adapting the application individually

8.3

Implementing more additional functions in the signal flow

_ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _ _

Configuring the list by means of parameterisation
The parameter list is combined similarly to the user menu via parameter setting. The following

application example shows the required procedure for configuring the list without using the

»Engineer« parameterisation dialog.
Task:
The parameters C00012, C00026/1 and C00027/1 are to be written.

1. Compiling the parameter list

Specify the given parameters in C01085/1 ... n in the <code>,<subcode> format:

• C01085/1 = 12.000
• C01085/2 = 26.001
• C01085/3 = 27.001
• C01085/4 ... n = 0.000 (no parameter)

2. Entering values for the parameters (value set 1)

In C01086/1 ... n, specify the values to be used to describe the selected parameters. The values

are entered according to the scaling format/scaling factor of the respective parameter.

• C01086/1 = <value> for list entry 1 (in our example: for parameter C00012)
• C01086/2 = <value> for list entry 2 (in our example: for parameter C00026/1)
• C01086/3 = <value> for list entry 3 (in our example: for parameter C00027/1)

These values are used in the writing process if the two bSelectWriteValue_1 and

bSelectWriteValue_2 inputs are not assigned or both set to FALSE.

3. Entering other values for the parameters (value sets 2 ... 4)

If required, up to three other sets can be set in the same way in C01087/1 ... n to C01089/1 ... n

which can optionally be written to the parameters. The decision as to which value set is finally

used is dependent upon the assignment of the two bSelectWriteValue_1 and

bSelectWriteValue_2 inputs:

4. Selecting a value set

The value set to be used in this example is selected via the free parameters DC00470/2...3 linked

to the selection inputs:

5. Activating the writing of the parameters

In this example, the parameter list is written via the free parameter C00470/1 linked to the

bExecute control input. A change from FALSE to TRUE in C00470/1 activates the writing of the

parameter list.

C00470/2 bSelectWriteValue_1

C00470/2 bSelectWriteValue_2 Value set used

FALSE

FALSE

Value set 1 (C01086/1 ... n)

TRUE

FALSE

Value set 2 (C01087/1 ... n)

FALSE

TRUE

Value set 3 (C01088/1 ... n)

TRUE

TRUE

Value set 4 (C01089/1 ... n)