2.3

Residual hazards

Protection of persons

Before working on the controller, check if no voltage is applied to

the power terminals because

• - depending on the device - the power terminals U, V, W, +UG,

- UG, Rb1 and Rb2 remain live for at least 3 ... 20 minutes after

disconnecting the mains.

• the power terminals L1, L2, L3; U, V, W, +UG, - UG, Rb1 and

Rb2 remain live when the motor is stopped.

Device protection

Connect/disconnect all pluggable terminals only in deenergised

condition!

Detach the controller from the installation, e.g. from the rear

panel of the control cabinet, only in deenergised condition!
Motor protection

With some settings of the controller, the connected motor can be

overheated.

• E.g. longer operation of the DC injection brake.

• Longer operation of self-ventilated motors at low speed.

Protection of the machine/plant

Drives can reach dangerous overspeeds (e. g. setting of high

output frequencies in connection with motors and machines not

suitable for this purpose)! The drive controllers do not provide

protection against such operating conditions. For this purpose,

use additional components.

Switch contactors in the motor cable only if the controller is

inhibited. When switching contactors in the motor cable while

the controller is enabled, you can activate monitoring functions

of the controller. If no monitoring function is activated,

switching is permissible.
Parameter set transfer

During the parameter set transfer, control terminals of the

controllers can adopt undefined states! Therefore it is required

to disable the terminal X4 (digital input signals) before the

transfer starts. This ensures that the controller is inhibited and

all control terminals have the firmly defined ”LOW” status.