Electrical installation

Wiring

4

l

13

KHB 13.0004−EN 2.1

Baud rates

Baud rate [kbps]

Length of the transmission cable [m]

9.6 ... 93.75

1200

187.5

1000

500

400

1500

200

3000

100

6000

100

12000

100

)

Note!

ƒ

The baud rate depends on the data volume, cycle time and number of bus
stations.

ƒ

The baud rate selected should be as low as possible. The lower the baud
rate, the more insensitive the PROFIBUS is to parasitic coupling.

I

Tip!

For high baud rates, we recommend to consider the application of optical
fibres.
Advantages of optical fibres:

ƒ

External electromagnetic interferences have no effects on the transmission
path.

ƒ

Bus lengths of several kilometres are also possible with higher baud rates.
The bus length is
– independent of the baud rate.
– depend on the optical fibre used.

Specification of the transmission cable

Please follow the specifications of the PROFIBUS user organisation (PUO) for signal cables:

Bus cable specification

Specific resistance

135 − 165

W/km, (f = 3 − 20 MHz)

Capacitance per unit length

£ 30 nF/km

Loop resistance

< 110

W/km

Core diameter

> 0.64 mm

Core cross−section

> 0.34 mm

2

Cores

Double twisted, insulated and shielded