Appendix, Table of parameter numbers (pnu) – Lenze 931K User Manual

Page 69

Advertising
background image

Appendix

Table of parameter numbers (PNU)

10

l

69

KHB 13.0004−EN 2.1

Characteristics

Possible settings

Name

PNU

Description

Selection

Lenze

Name

PNU

1022

Current Limitation

Selection of the torque
limitation independently of
the operating mode

0 Limit Current Input

Channel

0

Ċ

INT8

RW

Ċ

0

No limitation

Selection of the source for
the limitation

1

Limitation via AIN0

2

Limitation via AIN1

3

Limitation via RS232

7

Limitation via PROFIBUS

1 Limit Current

0

{1 mA}

40000

Ċ

INT32

RW

Ċ

Selection of the current value
to which the torque is
limited proportionally

l

For limitation via AIN0,
AIN1:
– The selected current

value is achieved at an
input voltage of 10 V

l

For limitation via RS232,
PROFIBUS:
– The current value is

specified directly

1040

Jog Value

Simplified access to the
inching values.
This type of access reduces
the amount of data to be
transferred in the cyclic data
telegram. Internally all
parameters are written.

0 Jog Velocity

100

0

{1 rpm}

6000

Ċ

INT32

RW

Ċ

Inching speed

l

The physical unit is the
PROFIBUS speed

1 Symmetrical Jog

Accelerations

10000

0

{1 rpm/s}

20000

Ċ

UINT32

RW

Ċ

Inching acceleration

l

The physical unit is the
PROFIBUS acceleration

l

The value read is the
acceleration

1050

0 Homing Method

1

Ċ

INT8

RW

Ċ

Homing to

Selection of the homing
method to be used.

1

the negative limit switch with zero
pulse evaluation

2

the positive limit switch with zero
pulse evaluation

17

the negative limit switch

18

the positive limit switch

33, 34

the zero pulse

35

the actual position (no movement)

−1

the negative end stop with zero pulse
evaluation

−2

the positive end stop with zero pulse
evaluation

−17

the negative end stop

−18

the positive end stop