Troubleshooting and fault elimination, Table of error messages – Lenze 931K User Manual

Page 65

Advertising
background image

Troubleshooting

and fault elimination

Table of error messages

9

l

65

KHB 13.0004−EN 2.1

Remedy

Cause

Response

Activation

time

Meaning

Error
number

Remedy

Cause

O

W

H

A

Activation

time

Meaning

Error
number

29

Following error monitoring

< 5 ms

ю ю ю ¨ Motor is blocked.

l

Optimise controller setting to improve the smooth
running characteristics.

l

Adapt travel profile (e.g. reduce acceleration and
deceleration ramps).

l

Increase following error margin/response delay.

31

Limit switch error

< 1 ms

ю ю ю ¨ Incorrect configuration of limit switch.

Check limit switch configuration.

Incorrect wiring of limit switch.

Ensure correct wiring of limit switch.

Limit switch defective.

Replace limit switch.

35

Time−out at quick stop

< 5 ms

þ ¨ ¨ ¨ Angle encoder error occurred.

Check encoder.

Motor identification failed.

Repeat motor identification.

Acceleration too high.

Check settings.

36

Homing error

< 5 ms

ю ю ю ¨ Homing run completed with errors.

Check homing configuration.

Incorrect parameter setting for controller
and angle encoder.

Check settings of controller and angle encoder.

40

Error: Motor and angle
encoder identification

< 5 ms

þ ¨ ¨ ¨ Homing run completed with errors.

l

Check resolver plug connection.

l

Check resolver cable for open or short circuit.

l

Check pin assignment of resolver cable plug.

Incorrect parameter setting for controller
and angle encoder.

Check settings of controller and angle encoder.

43

Course program: Unknown
command

< 5 ms

ю ю ¨ ¨

Contact Lenze.

44

Course program: Invalid jump
target

< 5 ms

ю ю ¨ ¨

l

The digital inputs for START1 and
START2 are set at the same time.

l

The jump target or the target position
is invalid.

Correct the settings.

55

PROFIBUS communication
error

< 5 ms

ю ю ю ¨

l

Communication is interfered

l

Check installation with regard to EMC requirements.

l

Double nodes in network

l

Check node number setting

56

RS232 communication error

< 5 ms

ю ю ю ¨ Communication is interfered.

Ensure EMC−compliant wiring.

57

Position data set error

< 5 ms

þ ¨ ¨ ¨ Conflict between acceleration and selected

travelling speed.

Contact Lenze.

58

Faulty operating mode

< 5 ms

ю ю ю ¨ Selection of wrong operating mode.

Switch to the correct operating mode while the power stage
is switched on.

60

Error in preliminary
positioning calculation

< 5 ms

þ ¨ ¨ ¨ Internal error.

Contact Lenze.

62

Stack overflow

< 5 ms

þ ¨ ¨ ¨

63

Checksum error

< 5 ms

þ ¨ ¨ ¨

64

Initialisation error

< 5 ms

ю ¨ ¨ ¨