4 state diagram, State diagram, Device control – Lenze 931K User Manual

Page 59

Advertising
background image

Device control

State diagram

Status word 1

8

l

59

KHB 13.0004−EN 2.1

8.4

State diagram

Power on

(1)

(2)

(8)

(7)

(9)

(3)

(6) (12)

(5)

(10)

(11)

(4)

S1: SWITCHING_ON_INHIBITED

S2: READY_FOR_SWITCH_ON

S3: SWITCHED_ON

S4:OPERATION

931e_027

Fig. 10

Simplified state diagram

Controller states

Status word 1

State

Bit 6

Bit 2

Bit 1

Bit 0 Description

0040

h

0004

h

0002

h

0001

h

Power on

Switch−on and initialisation of the controller.
Communication via PROFIBUS is not yet possible.

SWITCHING_ON_INHIBITED

1

0

0

0

The initialisation is completed.
The power stage is deactivated, the motor
produces zero torque.
Communication via PROFIBUS is possible.
The controller changes to this state when an error
message occurs.

READY_FOR_SWITCH_ON

0

0

0

1

Waiting for the controller to be enabled.
The controller can be enabled via DIN9 = HIGH or
via the controller enable logic "DIN9 and
PROFIBUS".

SWITCHED_ON

0

0

1

1

The controller is enabled (DIN9 = HIGH).

OPERATION

0

1

1

1

The controller is operating. The drive is controlled
according to the selected operating mode.

Advertising