5 commissioning with profidrive, Commissioning with profidrive, Commissioning – Lenze 931K User Manual

Page 37

Advertising
background image

Commissioning

"Positioning" mode

Commissioning with PROFIdrive

6

l

37

KHB 13.0004−EN 2.1

6.6.5

Commissioning with PROFIdrive

)

Note!

ƒ

The bit assignment of the control word 1 and the status word 1 is described
in the chapter "Device control". (

54)

ƒ

To enable the PLC to control the controller via PROFIBUS, bit 10 of the
control word 1 must be set statically. When the communication self−test has
been completed successfully, bit 9 of the status word 1 is set.

Description

PNU

Subind

ex

Length

Parameter

UNIT16

Bit 11

Bit 3

Bit 2

Bit 1

Bit 0

A

Running the controller up via the state machine

1.

Control word 1 (WO)
SWITCHING_ON_INHIBITED

967

0

16

0

0

1

1

0

2.

Status word 1 (RO)
SWITCHING_ON_INHIBITED

968

0

16

0

0

0

0

1

3.

Control word 1 (WO)
READY_FOR_SWITCH_ON

967

0

16

0

0

1

1

1

4.

Status word 1 (RO)
READY_FOR_SWITCH_ON

968

0

16

0

0

0

1

1

5.

Control word 1 (WO)
Enable operation

967

0

16

0

1

1

1

1

6.

Status word 1 (RO)
Operation

968

0

16

0

0

1

1

1

B

Execute homing

7.

Parameterise homing
Method via PNU 1050
Offset via PNU 1051
Accelerations via PNU 1001

8.

Control word 1 (WO)
Start

967

0

® 1

9.

Status word 1 (RO)

Homing not yet completed or has
failed with an error

968

0

Homing successfully completed

968

1

C

Control operation

10. Selection of setpoints

Note: Controller parameters
cannot be changed via PNUs.