Safety instructions

Thermal motor monitoring

Self−ventilated motors

2

l

125

EDKVF9333V DE/EN/FR 7.1

Calculate release time and I

2

x t load

Calculate the release time and the I

2

x t load of the motor considering the values in

C0129/1 and C0129/2(evaluation coefficient "y").

Formulae for release time

Information

y

+

100%

* C0129ń1

C0129

ń2

n

n

N

) C0129ń1

T

+ * ( t ) ln

ȧȧ

ȡ
Ȣ

1

*

z

) 1

ǒ

IMot

y

I

N

Ǔ

2

100

ȧȧ

ȣ
Ȥ

T

Release time of the I

2

x t monitoring

t

Thermal motor time constant (C0128)

In

Function: Natural logarithm

I

Mot

Actual motor current (C0054)

I

r

Rated motor current (C0088)

z

Threshold value in C0120 (OC6) or C0127 (OC8)

y

Evaluation coefficient

n

rated

Rated speed (C0087)

Formulae for I

2

x t load

Information

L(t)

+

ǒ

I

Mot

y

I

N

Ǔ

2

100%

ǒ

1

* e

*t

t

Ǔ

L(t)

Chronological sequence of the I

2

x t load of the motor

(Display: C0066)

y

Evaluation coefficient

I

Mot

Actual motor current (C0054)

Ir

Rated motor current (C0088)

t

Thermal motor time constant (C0128)

If the controller is inhibited, the I

2

x t load is reduced:

L(t)

+ L

Start

e

* tt

Ǹ

L

Start

I

2

x t load before controller inhibit

If an error is triggered, the value corresponds to the
threshold value set in C0120 (OC6) or C0127 (OC8).