Electrical installation

Important notes

5

l

159

EDKVF9333V DE/EN/FR 7.1

5

Electrical installation

5.1

Important notes

(

Stop!

The drive controller contains electrostatically sensitive components.
The personnel must be free of electrostatic charge when carrying out assembly
and service operations.

)

Note!

An earth−leakage circuit breaker between the supplying mains and the
controller can be activated by mistake ...

ƒ

by capacitive compensation currents of the cable shields during operation
(especially with long, shielded motor cables),

ƒ

by simultaneous connection of several controllers to the mains supply,

ƒ

if additional interference filters are used.

5.2

Installation according to EMC (installation of a CE−typical drive system)

ƒ

Connect all components (drive controller, choke, filter) to a central earthing point
(PE rail).

Mains connection, DC supply

ƒ

If a mains filter or RFI filter is used, install a shielded cable between mains filter or
RFI filter and drive controller if it is longer than 300 mm.

ƒ

For DC−bus operation or DC supply, use shielded cables.

Motor cables

ƒ

Use only shielded motor cables with braid made of tinned or nickel−plated copper.
Shields made of steel braid are not suitable.
– The overlap rate of the braid must be at least 70 % with an overlap angle of 90 °.

ƒ

Always connect the shield of the motor cable at both sides − at the drive controller
and at the motor.
– Always connect shields with a surface as large as possible to the conducting and

earthed mounting plate. Also use the shield connections on the device.

ƒ

The motor cable is perfectly installed if
– it is routed separately of mains cables and control cables,
– it crosses mains cables and control cables only at a right angle,
– it is not interrupted.