Mains choke/mains filter assignment, Electrical installation – Lenze EVF9333 User Manual

Page 194

Advertising
background image

Electrical installation

Standard devices in the power range 75 ... 90 kW
Mains choke/mains filter assignment

5

l

194

EDKVF9333V DE/EN/FR 7.1

Installation to UL

Supply conditions

Range

Description

Fuses

l

Only according to UL 248

l

Mains short−circuit current up to 10000 A

rms

: All classes permissible

l

Mains short−circuit current up to 50000 A

rms

: Only classes "J", "T" or "R" permissible

Cables

l

Only in accordance with UL

l

The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C

Observe all national and regional regulations!

Operation at rated power

9300

Rated fuse current

Cable cross−section

Fuse

L1, L2, L3, PE

Type

[A]

[AWG]

Operation with mains choke/mains filter

EVF9332−xV

175

2/0

EVF9333−xV

200

3/0

5.7.4

Mains choke/mains filter assignment

Operation at rated power

9300

Mains choke

Interference voltage category according to EN 61800−3 and motor cable length

Component

Component

Type

C2

max. [m]

C1

max. [m]

EVF9332−xV

ELN3−0022H130

EZN3A0022H150

25

E82ZN75334B230

10

E82ZN75334B230

50

EZN3B0022H150

50

EVF9333−xV

ELN3−0017H170

EZN3A0017H200

25

E82ZN90334B230

10

E82ZN90334B230

50

EZN3B0017H200

50

Operation with increased rated power

9300

Mains choke

Interference voltage category according to EN 61800−3 and motor cable length

Component

Component

Type

C2

max. [m]

C1

max. [m]

EVF9332−xV

ELN3−0017H170

EZN3A0017H200

25

E82ZN90334B230

10

E82ZN90334B230

50

EZN3B0017H200

50

EVF9333−xV

ELN3−0014H200

EZN3A0015H230

25

EZN3B0015H230

50

EZN3A0017H200

25

EZN3B0017H200

50