Technical data

General data and operating conditions

3

l

130

EDKVF9333V DE/EN/FR 7.1

Operating conditions

Ambient conditions

Climatic

Storage

IEC/EN 60721−3−1

1K3 (−25 ... +55 °C)

< 6 months

1K3 (−25 ... +40 °C)

> 6 months
> 2 years: form DC bus
capacitors

Transport

IEC/EN 60721−3−2

2K3 (−25 ... +70 °C)

Operation

EVF9321 ... EVF9326

IEC/EN 60721−3−3

3K3 (0 ... +55 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.

EVF9327 ... EVF9333

3K3 (0 ... +50 °C)
> +40 °C: reduce the rated output current by 2.5 %/°C.

Pollution

IEC/EN 61800−5−1

Degree of pollution 2

Site altitude

< 4000 m amsl
> 1000 m amsl: reduce the rated output current by
5 %/ 1000 m.

Mechanical

Vibration resistance
(9.81 m/s

2

= 1 g)

Germanischer Lloyd
5 ... 13.2 Hz

Amplitude ±1 mm 13.2 ... 100 Hz:
acceleration resistant up to 0.7 g

IEC/EN 60068−2−6
10 ... 57 Hz

Amplitude 0.075 mm 57 ... 150 Hz:
acceleration resistant up to 1 g

Electrical

AC−mains connection

Max. mains voltage
range

320 V − 0 % ... 528 V + 0 %

Mains frequency

45 Hz − 0 % ... 65 Hz + 0 %

Power system TT, TN

Operation permitted without restrictions with earthed
neutral.

Power system IT

Operation only permitted with the device variants V024 or
V100.
Operation permitted without restrictions with insulated
neutral.
Observe instructions on specific measures!

Operation on public
supply systems

EN 61000−3−2

Limitation of harmonic currents

Total output at the mains

Compliance with the
requirements

1)

< 1 kW

With mains choke.

> 1 kW

Without additional measures.

1)

The additional measures mentioned have the effect that solely the controllers

meet the requirements of EN 61000−3−2. The machine/system manufacturer is
responsible for the compliance with the requirements for the machine/system!

DC−mains connection

Max. mains voltage
range

450 V − 0 % ... 740 V + 0 %

Operating conditions

DC voltage must be symmetrical to PE.
The controller will be destroyed when +U

G

or −U

G

are earthed.

Motor connection

Length of the motor
cable

< 50 m

shielded

< 100 m

unshielded

At rated mains voltage and a switching frequency of

£ 8 kHz

without additional output filter.
For compliance with EMC regulations, the permissible cable
length might change.