Electrical installation

Standard devices in the power range 0.37 ... 11 kW

Mains connection: Fuses and cable cross−sections

5

l

165

EDKVF9333V DE/EN/FR 7.1

Mains connection, DC supply

L1 L2 L3 +UG -UG

PE

L1, L2, L3
+U , -U

G

G

0.5...0.6 Nm
4.4...5.3 lb-in

2

0
1

9300std033

Fig. 5−3

Mains connection, DC supply for drive controllers 0.37 ... 11 kW

0 Mains cable

1 Shield sheet

Securely clamp mains cable with the lugs

2 Mains and DC bus connection

L1, L2, L3: Connection of mains cable
+U

G

, −U

G

: Connection of DC−bus components or connection of the controller in the DC−bus

system (see system manual)
Cable cross−sections up to 4 mm

2

: Use wire end ferrules for flexible cables

Cable cross−sections > 4 mm

2

: Use pin−end connectors

5.4.3

Mains connection: Fuses and cable cross−sections

Installation in accordance with EN 60204−1

Supply conditions

Range

Description

Fuses

l

Utilisation category: only gG/gL or gRL

Cables

Laying systems B2 and C: Use of PVC−insulated copper cables, conductor temperature < 70 °C,
ambient temperature < 40 °C, no bundling of the cables or cores, three loaded cores. The data are
recommendations. Other dimensionings/laying systems are possible (e.g. in accordance with
VDE 0298−4).

RCCB

l

Controllers can cause a DC current in the PE conductor. If a residual current device (RCD) or a
fault current monitoring unit (RCM) is used for protection in the case of direct or indirect
contact, only one RCD/RCM of the following type can be used on the current supply side:
– Type B (universal−current sensitive) for connection to a three−phase system
– Type A (pulse−current sensitive) or type B (universal−current sensitive) for connection to a

1−phase system

Alternatively another protective measure can be used, like for instance isolation from the
environment by means of double or reinforced insulation, or isolation from the supply system
by using a transformer.

l

Earth−leakage circuit breakers must only be installed between mains supply and controller.

Observe all national and regional regulations!