Electrical installation – Lenze EVF9333 User Manual

Page 190

Advertising
background image

Electrical installation

Standard devices in the power range of 55 kW
Motor connection

5

l

190

EDKVF9333V DE/EN/FR 7.1

T1

T2

PE

U

V

W

2
3

0

1

U, V, W,
PE

M8
15 Nm
132 lb-in

}

+

PE

M5 x 12
3 Nm (26.5 lb-in)

9300vec124

Fig. 5−19

Motor connection with KTY thermal sensor

0 PE stud

PE cable connection with ring cable lug

1 U, V, W

Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable.
Max. connectable cable cross−section: 120 mm

2

with ring cable lug

2 Shield clamps

Place shields of motor cable with large surface on the shield sheet and fasten with shield
clamps and M5 × 12 mm screws

3 Cable ties

Strain relief of motor cable

Advertising
This manual is related to the following products: