Electrical installation

Standard devices in the power range 0.37 ... 11 kW

Mains connection: Fuses and cable cross−sections

5

l

167

EDKVF9333V DE/EN/FR 7.1

Installation to UL

Supply conditions

Range

Description

Fuses

l

Only in accordance with UL 248

l

System short−circuit current up to 5000 A

rms

: All classes are permissible

l

System short−circuit current up to 50000 A

rms

: Only classes "CC", "J", "T" or "R" permissible

Cables

l

Only in accordance with UL

l

The cable cross−sections specified in the following apply under the following conditions:
– Conductor temperature < 60 °C
– Ambient temperature < 40 °C

Observe all national and regional regulations!

Operation at rated power

9300

Rated fuse current

Cable cross−section

Fuse

L1, L2, L3, PE

Type

[A]

[AWG]

Operation without mains choke/mains filter

EVF9321−xV

6

18

EVF9322−xV

6

18

EVF9323−xV

10

16

EVF9325−xV

25

10

Operation with mains choke/mains filter

EVF9321−xV

6

18

EVF9322−xV

6

18

EVF9323−xV

10

16

EVF9324−xV

10

16

EVF9325−xV

25

10

EVF9326−xV

25

10

Max. connection cross−section of the terminal strip: AWG 12, with pin−end connector AWG 10