Technical data

General data and operating conditions

3

l

129

EDKVF9333V DE/EN/FR 7.1

3

Technical data

3.1

General data and operating conditions

General data

Conformity and approval

Conformity

CE

2006/95/EC

Low−Voltage Directive

2004/108/EG

EMC Directive

Approval

UL

cULus

Power Conversion Equipment (File No. E132659)

Protection of persons and equipment

Type of protection

EN 60529

IP20

IP41 in case of thermally separated installation (push−through
technique) between the control cabinet (inside) and the
environment.

NEMA 250

Protection against accidental contact in accordance with type
1

Earth leakage current

IEC/EN 61800−5−1

> 3.5 mA AC
> 10 mA DC

Observe regulations and safety
instructions!

Insulation of control
circuits

IEC/EN 61800−5−1

Safe mains isolation by double (reinforced) insulation for the
terminals X1 and X5.
Basic insulation (single isolating distance) for the terminals
X3, X4, X6, X8, X9, X10 and X11.

Insulation resistance

IEC/EN 61800−5−1

< 2000 m site altitude: overvoltage category III

> 2000 m site altitude: overvoltage category II

Protective measures

Against short circuit, earth fault (earth−fault protected during
operation, limited earth−fault protection during operation),
overvoltage, motor stalling, motor overtemperature (input for
PTC or thermal contact)

EMC

Noise emission

IEC/EN 61800−3

Cable−guided, up to 10 m motor cable length with mains
filter A: category C2.

Radiation, with mains filter A and installation in control
cabinet: category C2

Interference immunity

IEC/EN 61800−3

Category C3