Electrical installation

Wiring of the system bus (CAN)

5

l

206

EDKVF9333V DE/EN/FR 7.1

5.9

Wiring of the system bus (CAN)

Installation material required from the scope of supply:

Description

Use

Quantity

Terminal strip, 3−pole

Connection of system bus (CAN) at X4

1

Wiring

A

1

A

2

A

3

A

n

93XX

93XX

93XX

GND

GND

GND

GND

LO

LO

LO

LO

HI

HI

HI

HI

X4

X4

X4

PE

PE

PE

PE

120

120

9300VEC054

Fig. 5−30

System bus (CAN) wiring

A

1

Bus device 1 (controller)

A

2

Bus device 2 (controller)

A

3

Bus device 3 (controller)

A

n

Bus device n (e. g. PLC), n = max. 63

X4/GND

CAN−GND: System bus reference potential

X4/LO

CAN−LOW: System bus LOW (data line)

X4/HI

CAN−HIGH: System bus HIGH (data line)

(

Stop!

Connect a 120

W terminating resistor to the first and last bus device.

We recommend the use of CAN cables in accordance with ISO 11898−2:

CAN cable in accordance with ISO 11898−2

Cable type

Paired with shielding

Impedance

120

W (95 ... 140 W)

Cable resistance/cross−section

Cable length

£ 300 m £ 70 mW/m / 0.25 … 0.34 mm

2

(AWG22)

Cable length 301 … 1000 m

£ 40 mW/m / 0.5 mm

2

(AWG20)

Signal propagation delay

£ 5 ns/m