Electrical installation, Operation at rated power, Operation with increased rated power – Lenze EVF9333 User Manual

Page 166

Advertising
background image

Electrical installation

Standard devices in the power range 0.37 ... 11 kW
Mains connection: Fuses and cable cross−sections

5

l

166

EDKVF9333V DE/EN/FR 7.1

Operation at rated power

9300

Rated fuse current

Cable cross−section

FI

1)

Fuse

Circuit−breaker

Laying system L1, L2, L3, PE

B2

C

Type

[A]

[A]

[mm

2

]

[mm

2

]

[mA]

Operation without mains choke/mains filter

EVF9321−xV

6

C6, B6

2)

1

1

300

EVF9322−xV

6

C6, B6

2)

1

1

EVF9323−xV

10

B10

1.5

1

EVF9325−xV

25

B20

4

2.5

Operation with mains choke/mains filter

EVF9321−xV

6

C6, B6

2)

1

1

300

EVF9322−xV

6

C6, B6

2)

1

1

EVF9323−xV

10

B10

1.5

1

EVF9324−xV

10

B10

1.5

1

EVF9325−xV

20

B16

2.5

2.5

EVF9326−xV

32

B25

˘

4

1)

Universal current−sensitive earth−leakage circuit breaker

2)

For short−time mains interruptions, use circuit breakers with tripping characteristic "C"

Operation with increased rated power

9300

Rated fuse current

Cable cross−section

FI

1)

Fuse

Circuit−breaker

Laying system L1, L2, L3, PE

B2

C

Type

[A]

[A]

[mm

2

]

[mm

2

]

[mA]

Operation with mains choke/mains filter

EVF9321−xV

6

C6, B6

2)

1

1

300

EVF9322−xV

6

C6, B6

2)

1

1

EVF9323−xV

10

B10

1.5

1

EVF9324−xV

10

B10

1.5

1

EVF9325−xV

20

B16

2.5

2.5

1)

Universal current−sensitive earth−leakage circuit breaker

2)

For short−time mains interruptions, use circuit breakers with tripping characteristic "C"

Advertising
This manual is related to the following products: