Electrical installation
Control terminals
Important notes
l
200
EDKVF9333V DE/EN/FR 7.1
Terminal data
(
Stop!
ƒ
Connect or disconnect the terminal strips only if the controller is
disconnected from the mains!
ƒ
Wire the terminal strips before connecting them!
ƒ
Unused terminal strips must also be plugged on to protect the contacts.
Cable type
Wire end ferrule
Maximum cable
cross−section
Tightening torque Stripping
length
Rigid
—
2.5 mm
2
(AWG 14)
0.5 ... 0.6 Nm
(4.4 ... 5.3 lb−in)
5 mm
Flexible
Without wire end
ferrule
2.5 mm
2
(AWG 14)
Flexible
Wire end ferrule
without plastic sleeve
2.5 mm
2
(AWG 14)
Flexible
Wire end ferrule with
plastic sleeve
2.5 mm
2
(AWG 14)
Advertising