Electrical installation – Lenze EVF9333 User Manual

Page 175

Advertising
background image

Electrical installation

Standard devices in the power range 15 ... 30 kW

Mains connection, DC supply

5

l

175

EDKVF9333V DE/EN/FR 7.1

PE

+UG

-UG

L1

L2

L3

3

0

1

2

L1, L2, L3
+U , -U
PE

G

G

M6
5 Nm
44 lb-in

}

+

PE

9300std034

Fig. 5−9

Mains connection, DC supply for drive controllers 15 ... 30 kW

0 PE stud

Connect PE cable with ring cable lug

1 Conductive surface

2 Shield clamp

Place shield with large surface on control cabinet mounting plate and fasten with shield
clamp (shield clamp is not part of the scope of supply)
To improve the shield connection, also place the shield on the PE stud

3 Mains and DC bus connection

L1, L2, L3: Connection of mains cable with ring cable lugs
+U

G

, −U

G

: Connection of DC−bus components or connection of the controller in the DC−bus

system (see system manual)