Electrical installation – Lenze EVF9333 User Manual

Page 160

Advertising
background image

Electrical installation

Installation according to EMC (installation of a CE−typical drive system)

5

l

160

EDKVF9333V DE/EN/FR 7.1

Control cables

ƒ

For lengths of 200 mm and more, use only shielded cables for analog and digital
inputs and outputs. Under 200 mm, unshielded but twisted cables may be used.

ƒ

Connect the shield correctly:
– The shield connections of the control cables must be at a distance of at least

50 mm from the shield connections of the motor cables and DC cables.

– For cables for digital inputs and outputs, connect the shield at both ends.
– For cables for analog inputs and outputs, only connect the shield at the drive

controller end.