Electrical installation

Standard devices in the power range 15 ... 30 kW
Motor connection

5

l

178

EDKVF9333V DE/EN/FR 7.1

5.5.5

Motor connection

)

Note!

ƒ

Fusing the motor cable is not required.

ƒ

The drive controller features 2 connections for motor temperature
monitoring:
– Terminals T1, T2 for connecting a PTC thermistor or thermal contact

(NC contact).

– Pins X8/5 and X8/8 of the incremental encoder input (X8) for connecting a

KTY thermal sensor.

Shield sheet installation

(

Stop!

Do not use lugs as strain relief.

PE

T1

T2

U

V

W

a

3.4 Nm
30 lb-in

a

0

9300vec131

Fig. 5−10

Installation of shield sheet for drive controllers 15 ... 30 kW

0 Fasten the shield sheet with two self−tapping screws Ж 4 Ч 14 mm (a)

Motor with PTC thermistor or thermal contact (NC contact)

Wire T1, T2 only if the motor is equipped with a PTC thermistor or thermal contact
(NC contact).

ƒ

An "open" cable acts like an antenna and can cause faults on the drive controller.

{

Danger!

ƒ

Alle Steuerklemmen sind nach dem Anschluss eines Kaltleiters (PTC) oder
eines Thermokontakts nur noch basisisoliert (einfache Trennstrecke).

ƒ

Berührsicherheit bei defekter Trennstrecke ist nur durch externe
Maßnahmen gewährleistet, z. B. doppelte Isolierung.