Standard devices in the power range 75 ... 90 kW

Motor connection

5

l

195

EDKVF9333V DE/EN/FR 7.1

5.7.5

Motor connection

)

Note!

ƒ

Fusing the motor cable is not required.

ƒ

The drive controller features 2 connections for motor temperature
monitoring:
– Terminals T1, T2 for connecting a PTC thermistor or thermal contact

(NC contact).

– Pins X8/5 and X8/8 of the incremental encoder input (X8) for connecting a

KTY thermal sensor.

Motor with PTC thermistor or thermal contact (NC contact)

Wire T1, T2 only if the motor is equipped with a PTC thermistor or thermal contact
(NC contact).

ƒ

An "open" cable acts like an antenna and can cause faults on the drive controller.

{

Danger!

ƒ

Alle Steuerklemmen sind nach dem Anschluss eines Kaltleiters (PTC) oder
eines Thermokontakts nur noch basisisoliert (einfache Trennstrecke).

ƒ

Berührsicherheit bei defekter Trennstrecke ist nur durch externe
Maßnahmen gewährleistet, z. B. doppelte Isolierung.

PE U

V

W

T1 T2

+UG -UG

PES

PES

PE

M

3~

J>

PES

PES

PES

2.7 k

MONIT-OH8

15 V

3.3 k

7.4 k

9300vec139

Fig. 5−21

Circuit diagram of motor connection with PTC thermistor or thermal contact (NC contact) at T1, T2