Electrical installation
Standard devices in the power range 75 ... 90 kW
Motor connection
l
198
EDKVF9333V DE/EN/FR 7.1
T1
T2
PE
U
V
W
2
3
4
0
M4 x 12: 2.5 Nm (22.1 lb-in)
M5 x 12: 3 Nm (26.5 lb-in)
U, V, W,
PE
M10
30 Nm
264 lb-in
1
a
}
+
PE
9300vec125
Fig. 5−24
Motor connection with KTY thermal sensor
0 PE stud
PE cable connection with ring cable lug
1 U, V, W
Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable.
Max. connectable cable cross−section: 240 mm
2
with ring cable lug
2 Shield clamps
Place shields of motor cable with large surface on the shield sheet and fasten with shield
clamps and M5 × 12 mm screws
3 Cable ties
Strain relief of motor cable