Sicherheitshinweise

Sicherheitshinweise für die Installation nach UL

2

l

23

EDKVF9333V DE/EN/FR 7.1

2.4

Sicherheitshinweise für die Installation nach UL

J

Warnings!

ƒ

Motor Overload Protection
– For information on the protection level of the internal overload protection

for a motor load, see the corresponding manuals or software helps.

– If the integral solid state motor overload protection is not used, external or

remote overload protection must be provided.

ƒ

Branch Circuit Protection
– The integral solid state protection does not provide branch circuit

protection.

– Branch circuit protection has to be provided externally in accordance with

corresponding instructions, the National Electrical Code and any
additional codes.

ƒ

Please observe the specifications for fuses and screw−tightening torques in
these instructions.

ƒ

EVF9321 … EVF9326:
– Suitable for use on a circuit capable of delivering not more than 5000 rms

symmetrical amperes, 480 V maximum, when protected by fuses.

– Suitable for use on a circuit capable of delivering not more than 50000 rms

symmetrical amperes, 480 V maximum, when protected by CC, J, T or R
class fuses.

– Maximum surrounding air temperature: 0 ... +55 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 75 °C copper wire only.

ƒ

EVF9327 … EVF9329:
– Suitable for use on a circuit capable of delivering not more than 5000 rms

symmetrical amperes, 480 V maximum, when protected by fuses.

– Suitable for use on a circuit capable of delivering not more than 50000 rms

symmetrical amperes, 480 V maximum, when protected by J, T or R class
fuses.

– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.

ƒ

EVF9330 … EVF9333:
– Suitable for use on a circuit capable of delivering not more than 10000 rms

symmetrical amperes, 480 V maximum, when protected by fuses.

– Suitable for use on a circuit capable of delivering not more than 50000 rms

symmetrical amperes, 480 V maximum, when protected by J, T or R class
fuses.

– Maximum surrounding air temperature: 0 ... +50 °C
– > +40 °C: reduce the rated output current by 2.5 %/°C
– Use 60/75 °C or 75 °C copper wire only.