Electrical installation, Supply via internal voltage source – Lenze EVF9333 User Manual

Page 203

Advertising
background image

Electrical installation

Control terminals

Device variant with "Safe torque off" function

5

l

203

EDKVF9333V DE/EN/FR 7.1

Supply via internal voltage source

ƒ

If a freely assignable digital output (e.g. X5/A1) is assigned permanently to HIGH
level, it serves as an internal voltage source. Every output has a maximum load
capacity of 50 mA.
– The relay K

SR

and two digital inputs (X5/28 and e.g. X5/E1) can be supplied with

voltage via a digital output.

– Two digital outputs must be connected in parallel and assigned permanently to

HIGH level in order to obtain the maximum wiring (relays K

SR

and X5/E1 ... X5/E5,

X5/ST1).

ƒ

For the supply of the analog inputs (X6/1, X6/2 and X6/3, X6/4) you have to set a
freely assignable analog output (e. g. X6/63) permanently to HIGH level.

GND2

+24V

+5 V

DIGOUT4

E5

A2 A3 A4 ST1ST2 59

39

3k

47k

50mA

50mA

50mA

50mA

X5

28 E1 E2 E3 E4

3k

3k

3k

3k

3k

X11 K31 K32 33 34

S1

S2

IN1 IN2 IN3 IN4

+

K

SR

A1

Z1

X3

GND1

GND1

X6

1

2

3

4

7

7

62 63

242R

1
2
3
4
5
6

100k

100k

100k

100k

3.3nF

AIN1

AIN2

AOUTx

AOUT2

AOUT1

1

3

2

4

7

10k

10k

9300vec135

Fig. 5−28

Wiring of digital and analog inputs/outputs with active "Safe torque off" function and internal
voltage source

S1

Deactivate pulse inhibit (1st disconnecting path)

S2

Enable controller (2nd disconnecting path)

Z1

Programmable logic controller (PLC)
The PLC monitors the ˜Safe torque off˜ function

X5/A4 Feedback via a digital output (e. g. DIGOUT4)

NO contact or NC contact

Z

Load
Minimum wiring required for operation

Terminal assignment in the Lenze setting:

^ 205