Rockwell Automation Publication 193-UM012B-EN-P - June 2011

Chapter 4

6.

Set the Connection Parameters. I/O data is accessed using Input Instances
50, 51, 106, 110 or 111 and Output Instances 2, 101 or 103. The size of
the input connection and the output connection shall correspond to the
size of the chosen instance. The E1 Plus configuration assembly instance is
120. In this example configuration data is not used, so the data size is set to
0.

7.

Enter the IP address of the E1 Plus EtherNet/IP Side Mount Module.

8.

Click Next.

9.

Enter a value for the time between each scan of the module. Make sure
Inhibit Module is not checked.

10.

Click Finish to add the E1 Plus to the I/O Configuration in
RSLogix 5000.