The following common services are implemented for the Control Supervisor
Object:

101

Get

Warning Status

WORD

Bit 0=Overload
Bit 1=Not Used
Bit 2=Jam
Bit 3=Underload
Bit 4=Not Used
BIt 5=Comm Fault
Bit 6=Comm Idle
Bit 7=Non Vol Mem Fault
Bit 8-Bit 15=Not used

102

Get

Trip Log 0

WORD

Last trip condition. Bit definitions of the value are the same as attribute 101

103

Get

Trip Log 1

WORD

Last trip condition. Bit definitions of the value are the same as attribute 101

104

Get

Trip Log 2

WORD

Last trip condition. Bit definitions of the value are the same as attribute 101

105

Get

Trip Log 3

WORD

Last trip condition. Bit definitions of the value are the same as attribute 101

106

Get

Trip Log 4

WORD

Last trip condition. Bit definitions of the value are the same as attribute 101

107

Get

Device Status

WORD

Bit 0=Trip
Bit 1=Warning
Bit 2=OutputA
Bit 3=Input 1
Bit 4=Input 2
Bit 5=Motor Current
Bit 6-Bit 15=Not used

108

Get/Set

Trip Enable

WORD

Bit 0=Not Used
Bit 1=Not Used
Bit 2=Jam
Bit 3-Bit 15=Not Used

109

Get/Set

Warning Enable

WORD

Bit 0=Overload
Bit 1=Not Used
Bit 2=Jam
Bit 3=Underload
Bit 4=Not Used
BIt 5=Comm Fault
Bit 6=Comm Idle
Bit 7-Bit 15=Not Used

110

Get/Set

OL Reset Mode

BOOL

0=Manual
1=Automatic

111

Get/Set

IN1 Assignment

USINT

0=Normal
1=Trip Reset
2=OL Contact

112

Get/Set

IN2 Assignment

USINT

0=Normal
1=Trip Reset
2=OL Contact

Table 37 - Control Supervisor Object Instance 1 Attributes

Attribute ID

Access Rule

Name

Data Type

Value

Table 38 - Control Supervisor Object Common Services

Service
Code

Implemented for:

Service Name

Class

Instance

0x0E

No

Yes

Get Attribute Single

0x10

No

Yes

Set Attribute Single

0x05

No

Yes

Reset