Rockwell Automation Publication 193-UM012B-EN-P - June 2011

67

Chapter 6

Jam Inhibit Time

Parameter No.

18

This parameter defines the amount of time for
which jam detection is inhibited during a motor
starting sequence.

Access Rule

Get/Set

Data Type

USINT

Units

Seconds

Min. Value

0

Max. Value

250

Default Value

10

Tag Name

Jam_Inhibit_Time

Jam Trip Delay

Parameter No.

19

This parameter allows the installer to program a
time duration for which a jam condition must exist
at the programmed level prior to the device
tripping.

Access Rule

Get/Set

Data Type

USINT

Units

Seconds

Min. Value

5

Max. Value

250

Default Value

50

Tag Name

Jam_Trip_Delay

Jam Trip Level

Parameter No.

20

This parameter sets the jam trip level.

Access Rule

Get/Set

Data Type

UINT

Units

% FLA

Min. Value

150

Max. Value

600

Default Value

250

Tag Name

Jam_Trip_Level

Jam Warn Level

Parameter No.

21

This parameter sets the jam warning level.

Access Rule

Get/Set

Data Type

UINT

Units

% FLA

Min. Value

100

Max. Value

600

Default Value

150

Tag Name

Jam_Warn_Level