Chapter 6
Jam Inhibit Time
Parameter No.
18
This parameter defines the amount of time for
which jam detection is inhibited during a motor
starting sequence.
Access Rule
Get/Set
Data Type
USINT
Units
Seconds
Min. Value
0
Max. Value
250
Default Value
10
Tag Name
Jam_Inhibit_Time
Jam Trip Delay
Parameter No.
19
This parameter allows the installer to program a
time duration for which a jam condition must exist
at the programmed level prior to the device
tripping.
Access Rule
Get/Set
Data Type
USINT
Units
Seconds
Min. Value
5
Max. Value
250
Default Value
50
Tag Name
Jam_Trip_Delay
Jam Trip Level
Parameter No.
20
This parameter sets the jam trip level.
Access Rule
Get/Set
Data Type
UINT
Units
% FLA
Min. Value
150
Max. Value
600
Default Value
250
Tag Name
Jam_Trip_Level
Jam Warn Level
Parameter No.
21
This parameter sets the jam warning level.
Access Rule
Get/Set
Data Type
UINT
Units
% FLA
Min. Value
100
Max. Value
600
Default Value
150
Tag Name
Jam_Warn_Level