Rockwell Automation Publication 193-UM012B-EN-P - June 2011

47

Chapter 4

Users can read all of the motor diagnostic data back in one MSG instruction by
using Assembly Instance 111. An example of configuring a ControlLogix explicit
message using the MSG instruction to read all of the motor diagnostic data from
the E1 Plus EtherNet/IP Side Mount Module is shown below.

1.

Configure the configuration tab for the message instruction with the
follow settings:
• Message type: CIP Generic
• Service type: Get Attribute Single
• Class: 4 – the Assembly Object
• Instance: 111 - the Complete Motor Starter assembly
• Destination: The controller tag to write the data to.
• Attribute: 3 – get/set data instance attribute

2.

Configure the path field in the communications tab to point to the E1 Plus
EtherNet/IP Side Mount Module.

Path: 1, 2, 2, 192.168.0.100

For this example, 1 represents the processor slot, 2 represents the
EtherNet/IP scanner slot, 2 represents the EtherNet/IP port, and
192.168.0.100

represents the IP address of the E1 Plus EtherNet/IP Side

Mount Module.