Chapter 6

OutA En FltValue

Parameter No.

37

This parameter determines the state that Output A
assumes when a EtherNet/IP network fault occurs
and the FltState is set to “0”.
0 = Open
1 = Closed

Access Rule

Get/Set

Data Type

BOOL

Units

Min. Value

0

Max. Value

1

Default Value

0

Tag Name

OutA_En_FLTValue

OutA En IdlState

Parameter No.

38

This parameter, in conjunction with the IdlState,
defines how Output A will respond when the
EtherNet/IP network is idle (clear mode). When
set to “1”, Output A will hold the state prior to trip
occurrence. When set to “0”, Output A will open
or close. The En Flt parameters supersede the En
Idl parameters.
0 = Go to IdlValue
1 = Hold Last State

Access Rule

Get/Set

Data Type

BOOL

Units

Min. Value

0

Max. Value

1

Default Value

0

Tag Name

OutA_En_IdlState

OutA En IdlValue

Parameter No.

39

This parameter determines the state that Output A
assumes when the network is idle and instructed
by the IdlState parameter.
0 = Open
1 = Closed

Access Rule

Get/Set

Data Type

BOOL

Units

Min. Value

0

Max. Value

1

Default Value

0

Tag Name

OutA_En_IdlValue

IN1 Assignment

Parameter No.

40

This parameter allows the user to assign a
specific function to the discrete IN1 input.
0 = Normal
1 = Trip Reset
2 = OL Contact

Access Rule

Get/Set

Data Type

USINT

Units

Min. Value

0

Max. Value

2

Default Value

0

Tag Name

IN1_Assignment