Advanced setup group – Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual

Page 65

Advertising
background image

Rockwell Automation Publication 193-UM012B-EN-P - June 2011

65

Chapter 6

Advanced Setup Group

Trip Status

Parameter No.

3

This parameter provides trip identification.
1 = Trip
0 = No Trip

Bit 0: Overload — Tag Name: Trip_Status: Overload
Bit 1: Phase Loss — Tag Name: Trip_Status: Phase_Loss
Bit 2: Jam — Tag Name: Trip_Status: Jam

Access Rule

Get

Data Type

WORD

Units

—

Min. Value

0x0000

Max. Value

0x0007

Default Value

0x0000

Warning Status

Parameter
No.

4

This parameter provides warning identification
1 = Warning
0 = No Warning

Bit 0: Overload — Tag Name: Warning_Status: Overload
Bit 2: Jam — Tag Name: Warning_Status: Jam
Bit 3: Underload — Tag Name: Warning_Status: Underload
Bit 5: Comm Fault — Tag Name: Warning_Status: Comm_Fault
Bit 6: Comm Idle — Tag Name: Warning_Status: Comm_Idle
Bit 7: Non Vol Mem Fault — Tag Name: NV_Mem_Fault

Access Rule

Get

Data Type

WORD

Units

—

Min. Value

0x0000

Max. Value

0x00FF

Default Value

0x0000

Device Status

Parameter
No.

10

This parameter provides status information related to the E1 Plus
Overload Relay and the SMM.
1 = On or Present
0 = Off or Not Present
Bit 0: Trip — Tag Name: Device_Status: Trip
Bit 1: Warning — Tag Name: Device_Status: Warning
Bit 2: Output A — Tag Name: Device_Status: Out_A
Bit 3: Input #1 — Tag Name: Device_Status: In_1
Bit 4: Input #2 — Tag Name: Device_Status: In_2
Bit 5: Motor Current — Tag Name: Device_Status: Motor_Current

Access Rule

Get

Data Type

WORD

Units

—

Min. Value

0x0000

Max. Value

0x003F

Default
Value

0x0000

Trip Enable

Parameter No.

12

This parameter allows the installer to enable or
disable the Jam Trip function
1 = Enabled
0 = Disabled
Bit 2: Jam— Tag Name: Trip_Enable: Jam

Access Rule

Get/Set

Data Type

WORD

Units

—

Min. Value

0x0000

Max. Value

0x0007

Default Value

0x0000