Rockwell Automation Publication 193-UM012B-EN-P - June 2011

65

Chapter 6

Advanced Setup Group

Trip Status

Parameter No.

3

This parameter provides trip identification.
1 = Trip
0 = No Trip

Bit 0: Overload — Tag Name: Trip_Status: Overload
Bit 1: Phase Loss — Tag Name: Trip_Status: Phase_Loss
Bit 2: Jam — Tag Name: Trip_Status: Jam

Access Rule

Get

Data Type

WORD

Units

Min. Value

0x0000

Max. Value

0x0007

Default Value

0x0000

Warning Status

Parameter
No.

4

This parameter provides warning identification
1 = Warning
0 = No Warning

Bit 0: Overload — Tag Name: Warning_Status: Overload
Bit 2: Jam — Tag Name: Warning_Status: Jam
Bit 3: Underload — Tag Name: Warning_Status: Underload
Bit 5: Comm Fault — Tag Name: Warning_Status: Comm_Fault
Bit 6: Comm Idle — Tag Name: Warning_Status: Comm_Idle
Bit 7: Non Vol Mem Fault — Tag Name: NV_Mem_Fault

Access Rule

Get

Data Type

WORD

Units

Min. Value

0x0000

Max. Value

0x00FF

Default Value

0x0000

Device Status

Parameter
No.

10

This parameter provides status information related to the E1 Plus
Overload Relay and the SMM.
1 = On or Present
0 = Off or Not Present
Bit 0: Trip — Tag Name: Device_Status: Trip
Bit 1: Warning — Tag Name: Device_Status: Warning
Bit 2: Output A — Tag Name: Device_Status: Out_A
Bit 3: Input #1 — Tag Name: Device_Status: In_1
Bit 4: Input #2 — Tag Name: Device_Status: In_2
Bit 5: Motor Current — Tag Name: Device_Status: Motor_Current

Access Rule

Get

Data Type

WORD

Units

Min. Value

0x0000

Max. Value

0x003F

Default
Value

0x0000

Trip Enable

Parameter No.

12

This parameter allows the installer to enable or
disable the Jam Trip function
1 = Enabled
0 = Disabled
Bit 2: Jam— Tag Name: Trip_Enable: Jam

Access Rule

Get/Set

Data Type

WORD

Units

Min. Value

0x0000

Max. Value

0x0007

Default Value

0x0000