Input assemblies – Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual

Page 84

Advertising
background image

84

Rockwell Automation Publication 193-UM012B-EN-P - June 2011

Appendix B

Input Assemblies

Table 18 - Instance 50 — Trip Status Input Assembly from ODVA Overload Profile

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Tripped

Table 19 - Instance 51 —Basic Status Input Assembly from ODVA Overload Profile

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Warning

Tripped

Table 20 - Instance 106 —Motor Starter Input Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Motor
Current

Input 2

Input 1

Out A Stat Warning

Tripped

Table 21 - Instance 110 —Extended Motor Starter Input Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Motor
Current

Input 2

Input 1

Out A Stat Warning

Tripped

1

Unused

2

Average % FLA (low byte)

3

Average % FLA (high byte)

4

%Therm Utilized (low byte)

5

%Therm Utilized (high byte)

Table 22 - Instance 111 —Complete Motor Starter Input Assembly

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

0

Motor
Current

Input 2

Input 1

Out A Stat Warning

Tripped

1

Unused

2

Average % FLA (low byte)

3

Average % FLA (high byte)

4

%Therm Utilized (low byte)

5

%Therm Utilized (high byte)

6

Trip Status (low byte)

7

Trip Status (high byte)

8

Warning Status (low byte)

9

Warning Status (high byte)

10

Device Status (low byte)

11

Device Status (high byte)

12

Trip Log 0 (low byte)

13

Trip Log 0 (high byte)

14

Trip Log 1 (low byte)

15

Trip Log 1 (high byte)

Advertising