Rockwell Automation Publication 193-UM012B-EN-P - June 2011

61

Chapter 5

4.

Enter the Device Identity information into the fields as described below.

5.

Click "Apply Changes" to save the configuration.

Limitations

Based on the functionality of the E1 Plus EtherNet/IP module there are some
limitations on when emails can be triggered.

• If two events occur at the same time, an email will only be sent for the most

significant event.

• If the module has been configured to send an email for a lower prioritized

event and this event occurs at the same time as a higher prioritized event
for which the module has not been programmed to send an email, no email
will be sent for either event.

• The Clear email will only be sent when all events have been cleared and an

event email has previously been sent. For example: if the module is
configured to send an email when a jam trip is detected and it detects an
overload trip for which no email notification is configured, no email will be
sent when the overload event is cleared.

Device Name

The name of the E1 Plus EtherNet/IP module.

Device Description

The description of the E1 Plus EtherNet/IP module.

Device Location

The location of the E1 Plus EtherNet/IP module.

Contact Info

Contact information for the E1 Plus EtherNet/IP module.