Chapter 4

1.

Configure the configuration tab for the message instruction with the
follow settings:
• Message type: CIP Generic
• Service type: Parameter Read
• Instance: 10: The parameter you want to read back (e.g., 10 represents

device status)

• Destination: The controller tag to write the data to.

2.

Configure the path field in the communications tab to point to the E1 Plus
EtherNet/IP Side Mount Module.

Path: 1, 2, 2, 192.168.0.100

For this example, 1 represents the processor slot, 2 represents the
EtherNet/IP scanner slot, 2 represents the EtherNet/IP port, and
192.168.0.100

represents the IP address of the E1 Plus EtherNet/IP Side

Mount Module.