Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual
Page 46
Advertising
46
Rockwell Automation Publication 193-UM012B-EN-P - June 2011
Chapter 4
1.
Configure the configuration tab for the message instruction with the
follow settings:
• Message type: CIP Generic
• Service type: Parameter Read
• Instance: 10: The parameter you want to read back (e.g., 10 represents
device status)
• Destination: The controller tag to write the data to.
2.
Configure the path field in the communications tab to point to the E1 Plus
EtherNet/IP Side Mount Module.
Path: 1, 2, 2, 192.168.0.100
For this example, 1 represents the processor slot, 2 represents the
EtherNet/IP scanner slot, 2 represents the EtherNet/IP port, and
192.168.0.100
represents the IP address of the E1 Plus EtherNet/IP Side
Mount Module.