Reset/lock group – Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual

Page 68

Advertising
background image

68

Rockwell Automation Publication 193-UM012B-EN-P - June 2011

Chapter 6

Reset/Lock Group

UL Inhibit Time

Parameter No.

22

This parameter defines the amount of time for
which underload detection is inhibited during a
motor starting sequence.

Access Rule

Get/Set

Data Type

USINT

Units

Seconds

Min. Value

0

Max. Value

250

Default Value

10

Tag Name

UL_Inhibit_Time

UL Warn Level

Parameter No.

23

This parameter sets the underload warning level.

Access Rule

Get/Set

Data Type

USINT

Units

% FLA

Min. Value

30

Max. Value

100

Default Value

70

Tag Name

UL_Warn_Level

Trip Reset

Parameter No.

14

This parameter provides the user with the
capability of resetting a trip over the EtherNet/IP
network. After a trip is reset, the parameter
automatically returns to a “Ready” state.
0 = Ready
1 = Reset Trip
Note: A transition from 0 to 1 is necessary to
trigger a trip reset when mapped on the cyclic
data.

Access Rule

Get/Set

Data Type

BOOL

Units

Min. Value

0

Max. Value

1

Default Value

0

Tag Name

Trip_Reset

Program Lock

Parameter No.

24

This parameter prohibits the device parameters
from being altered when set to “Locked”. It must
be set to “Unlocked” to allow parameter
modification.
It doesn’t affect parameters when they’re
accessed through the assembly object.
0 = Unlocked
1 = Locked

Access Rule

Get/Set

Data Type

BOOL

Units

Min. Value

0

Max. Value

1

Default Value

0

Tag Name

Program_Lock