Rockwell Automation Publication 193-UM012B-EN-P - June 2011
49
Chapter 4
• Class: 4 – the Assembly Object
• Instance: 111 – the Complete Motor Starter assembly
• Attribute: 3 – get/set data instance attribute
3.
Configure MultiHop tab in the MSG instruction with the following
parameters:
To Address: the IP address of the E1 Plus EtherNet/IP Side Mount
Module.
An example of a MicroLogix 1100 using the MSG instruction to write data to
energize an output relay on the E1 Plus EtherNet/IP Side Mount Module is
shown below.