The following instance attributes are supported for all parameter group instances:

The following common services are implemented for the Parameter Group
Object:

Control Supervisor Object — CLASS CODE 0x29

No class attributes are supported for the Control Supervisor Object. A single
instance (instance 1) of the Control Supervisor Object is supported. The
following instance attributes are supported.

Table 35 - Parameter Group Object Instance Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Group Name String

SHORT_STRING

N/A

2

Get

Number of Members

UINT

N/A

3

Get

1st Parameter

UINT

N/A

4

Get

2nd parameter

UINT

N/A

n

Get Nth

Parameter

UINT

N/A

Table 36 - Parameter Group Object Common Services

Service
Code

Implemented for:

Service Name

Class

Instance

0x0E

Yes

Yes

Get Attribute Single

Table 37 - Control Supervisor Object Instance 1 Attributes

Attribute ID

Access Rule

Name

Data Type

Value

10

Get

Faulted

BOOL

0=No Fault present
1= Fault Latched

11

Get

Warning

BOOL

0=No Warnings present
1=Warning present (not latched)

12

Get/Set

Fault Rst

BOOL

0=No action
0->1=Fault reset

13

Get

FaultCode

UINT

If in Faulted state, FaultCode indicates the fault that caused the transition to
Faulted state. If not in Faulted state, FaultCode indicates the fault that
caused the last transition to the Faulted state.

14

Get Warning

Code

UINT

Code

word

indicating warning present. If multiple warnings are present, the

lowest code value is displayed.

100

Get

Trip Status

WORD

Bit 0=Overload
Bit 1=Phase Loss
Bit 2=Jam
Bit 3-Bit 15=Not used