I/o setup group – Rockwell Automation 193-ETN E1 Plus EtherNet Side Mount Module User Manual User Manual

Page 69

Advertising
background image

Rockwell Automation Publication 193-UM012B-EN-P - June 2011

69

Chapter 6

I/O Setup Group

Set To Defaults

Parameter No.

25

This parameter allows the user to reset the
parameter settings to the factory default values.
After parameter values have been reset to the
factory default settings, the parameter
automatically returns to a “Ready” state.
0 = Ready
1 = Reset Defaults
Note: A transition from 0 to 1 is necessary to
trigger a set to default when mapped on the cyclic
data.

Access Rule

Get/Set

Data Type

BOOL

Units

Min. Value

0

Max. Value

1

Default Value

0

Tag Name

Set_To_Default

OutA Pr FltState

Parameter No.

34

This parameter, in conjunction with the Pr
FltValue, defines how Output A will respond when
a trip occurs. When set to “1”, Output A will
continue to operate as commanded via the
network. When set to “0”, Output A will open or
close as determined by the setting of the Pr
FltValue.
0 = Go to FltValue
1 = Ignore Fault

Access Rule

Get/Set

Data Type

BOOL

Units

Min. Value

0

Max. Value

1

Default Value

0

Tag Name

OutA_Pr_FLTState

OutA Pr FltValue

Parameter No.

35

This parameter determines the state that Output A
assumes when a trip occurs and the Pr FltState is
set to “0”.
0 = Open
1 = Closed

Access Rule

Get/Set

Data Type

BOOL

Units

Min. Value

0

Max. Value

1

Default Value

0

Tag Name

OutA_Pr_FLTValue

OutA En FltState

Parameter No.

36

This parameter, in conjunction with the FltValue,
defines how Output A will respond when a
EtherNet/IP network fault occurs. When set to
“1”, Output A will hold the state prior to trip
occurrence. When set to “0”, Output A will open
or close as determined by the setting of the
FltValue.
0 = Go to FltValue
1 = Hold Last State

Access Rule

Get/Set

Data Type

BOOL

Units

Min. Value

0

Max. Value

1

Default Value

0

Tag Name

OutA_En_FLTState