Identity Object instances contain the following instance attributes:

The following common services are implemented for the Identity Object:

Message Router Object — CLASS CODE 0x02

No class or instance attributes are supported. The message router object exists
only to rout explicit messages to other objects.

Table 11 - Identity Object Instance Attributes

Attribute ID

Access Rule

Name

Data Type

Value

1

Get

Vendor ID

UINT

Programmable via test object

2

Get Device

Type

UINT

0x0003

3

Get

Product Code

UINT

300

4

Get Revision

Structure

of:

Major Revision

USINT

1

Minor Revision

USINT

N/A

5

Get

Status

WORD

Bit 0: Owned, shall be set when at least one connection i
configured
Bit 1: Reserved, set to 0
Bit 2: Configured
Bit 3: Reserved, set to 0
Bit 4-7: See extended device status
Bit 8: Minor Recoverable fault
BIt 9: Minor Unrecoverable fault
Bit 10: Major Recoverable fault
Bit 11: Major Unrecoverable fault
Bit 12-15: Reserved, set to 0
Extended device status (Bit 4-7)
0000=Unknown
0001=Firmware updated in progress
0010=Faulted I/O connection
0011=No I/O connection established
0100=Non volatile configuration bad
0101=Major fault
0110=Connection in run mode
0111=Connection in idle mode

6

Get

Serial Number

UDINT

Unique number assigned for each device

7

Get

Product Name

SHORT_STRING

Product name

8

Get State

USINT

3=Operational

Table 12 - Identity Object Common Services

Service Code

Implemented for:

Service Name

Class

Instance

0x01

No

Yes

Get Attribute All

0x0E

Yes

Yes

Get Attribute Single

0x05

No

Yes

Reset