Rockwell Automation 1336T FORCE Series B User Manual
Page 157

Chapter 5
Programming Parameters
5–31
Drive Software Version
[Drive SIO Version]
Parameter Number
01
Parameter Type
Source
Display Units
x.xx
Drive Units
Display units x 100
Factory Default
1.01
Minimum Value
0.00
Maximum Value
9.99
Power Structure Type
[Drive Type]
Parameter Number
05
Parameter Type
Source
Display Units
x
Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
65635
This parameter stores the present software
revision for the firmware product.
The firmware value represents the soft-
ware version in the range 00.0 to 99.9.
This number is a unique code that identi-
fies the drive’s current and voltage ratings.
This number originates from a serial EE
memory located on the Drive’s Base Drive
Board.
Motor Control Counter
[MCB Counter]
Parameter Number
08
Parameter Type
Source
Display Units
x.x sec
Drive Units
None
Factory Default
x 10 sec
Minimum Value
0.0 sec
Maximum Value
65535.5 sec
This parameter contains a counter that
increments by 1 every 0.1 seconds. It is
intended to be a monitor parameter to
indicate that the Motor Control Board
Velocity Processor firmware is executing.
Drive Link Task Interval
[D2D Tsk Interval]
Parameter Number
09
Parameter Type
Sink
Display Units
x ms
Drive Units
x/2
Factory Default
2
Minimum Value
1
Maximum Value
10
Drive Link Baud Rate
[D2D Baud Rate]
Parameter Number
10
Parameter Type
Sink
Display Units
Kbaud
Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
2
Drive Link Transmit Address
[D2D Xmit Addr]
Parameter Number
11
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
64
This parameter specifies the interval at
which drive to drive data will be transmitted
and received. The intervals are 2 ms
intervals up to 20 ms.
1 = 2 ms scan
2 = 4 ms scan
5 = 10 ms scan
8 = 16 ms scan
3 = 6 ms scan
6 = 12 ms scan
9 = 18 ms scan
4 = 8 ms scan
7 = 14 ms scan
10 = 20 ms scan
This word parameter specifies the baud
rate used on the drive-to-drive link (CAN)
communication interface as follows:
00H = 125K baud
01H = 250K baud
02H = 500K baud
This parameter specifies the node address
at which two words of data will be trans-
mitted. A value of zero disables the trans-
mit function.
Drive Link Receive 1 Address
[D2D Rcv 1 Addr]
Parameter Number
12
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
64
This parameter specifies the node address
at which two words of data will be
received. A value of zero disables the
receive function.
Refer to Document Update