Rockwell Automation 1336T FORCE Series B User Manual
Page 158

Chapter 5
Programming Parameters
5–32
Drive Link Receive 2 Address
[D2D Rcv 2 Addr]
Parameter Number
13
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
0
Minimum Value
0
Maximum Value
64
Drive Link Transmit Indirect 1
[D2D Xmit Ind 1]
Drive Link Transmit Indirect 2
[D2D Xmit Ind 2]
Parameter Number
15
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
21
Minimum Value
1
Maximum Value
219
Parameter Number
14
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
20
Minimum Value
1
Maximum Value
219
This is a word parameter defining the pa-
rameter number which data will be fetched
from to be transmitted in the high speed
communication network (CAN) for the first
word location of the transmitted message.
This is a word parameter defining the pa-
rameter number which data will be fetched
from to be transmitted in the high speed
communication network (CAN) for the 2nd
word location of the transmitted message.
This parameter specifies the node address
at which two words of data will be
received. A value of zero disables the
receive function.
Drive Link Receive 1, Indirect 1
[D2D Rcv 1, Ind 1]
Parameter Number
16
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
22
Minimum Value
1
Maximum Value
219
Drive Link Receive 1, Indirect 2
[D2D Rcv 1, Ind 2]
Parameter Number
17
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
23
Minimum Value
1
Maximum Value
219
Drive Link Receive 2, Indirect 1
[D2D Rcv 2, Ind 1]
Drive Link Receive 2, Indirect 2
[D2D Rcv 2, Ind 2]
Parameter Number
19
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
25
Minimum Value
1
Maximum Value
219
Parameter Number
18
Parameter Type
Sink
Display Units
x
Drive Units
None
Factory Default
24
Minimum Value
1
Maximum Value
219
This parameter specifies the parameter
number where the first word of data will be
put after it has been received from the
drive to drive communication.
This parameter specifies the parameter
number where the second word of data will
be put after it has been received from the
drive to drive communication.
This parameter specifies the parameter
number where the first word of data will be
put after it has been received from the
drive to drive communication.
This parameter specifies the parameter
number where the second word of data will
be put after it has been received from the
drive to drive communication.