Power wiring – Rockwell Automation 1336T FORCE Series B User Manual
Page 41

Chapter 2
Installation/Wiring
2–21
Power Wiring
On 1 to 30 HP drives, input and output power connections are performed
through a 10 position terminal block, TB1 located on the Gate Driver
Board. On drives larger than 30 HP, input and output power connections
are made at seperate terminal strips located at the bottom of the drive. The
drive connections are illustrated in Figure 2.10. The C thru G
configurations of TB1 are stud terminations and require the use of lug type
connectors to terminate the field installed conductors. Cat. No.
1336–LUG–XXXX Lug Kits are available for use with these
configurations of TB1. The wire size used is determined by selecting the
proper lug kit based on the Cat. No. of the drive. Refer to Table 2.C to
determine the correct lug kit for your application.
Figure 2.10.
Terminal Block TB1
PE
PE
R
(L1)
S
(L2)
T
(L3)
U
(T1)
V
(T2)
W
(T3)
DC
+
DC
–
Required
1
Input Fusing
AC Input Line
To Motor
200–240V, 7.5–11 kW (10–15 HP) Terminal Designations
380–480V, 15–22 kW (20–30 HP) Terminal Designations
500–600V, 15 kW (20 HP) Terminal Designations
Dynamic Brake
To Motor
1
Required Branch
Circuit Disconnect
B1
Frame
B2
Frame
PE
PE
R
(L1)
S
(L2)
T
(L3)
U
(T1)
V
(T2)
W
(T3)
DC
+
DC
–
AC Input Line
To Motor
To Motor
200–240V, 0.75–5.5 kW (1–7.5 HP) Terminal Designations
380–480/500–600V, 0.75–11 kW (1–15 HP) Terminal Designations
Dynamic Brake
Required
1
Input Fusing
1
Required Branch
Circuit Disconnect