Rockwell Automation 1336T FORCE Series B User Manual
Page 252

Appendix A
A–4
Table A.2
Maximum Motor Cable Length Restrictions in meters (feet) – 500V-600V Drives
4
No External Devices
w/ 1204-TFB2 Terminator
w/ 1204-TFA1 Terminator
Reactor at Drive
2
Motor w/ Insulation V
P–P
Motor w/ Insulation V
P–P
Motor w/ Insulation V
P–P
Motor w/ Insulation V
P–P
1000V
1200V
1600V
6
1000V
1200V
1600V
6
1000V
1200V
1600V
6
1000V
1200V
1600V
6
Drive Frame
Drive kW
(HP)
Motor kW
(HP)
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
Any
Cable
A4
0.75 (1)
0.75 (1)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.37 (0.5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.5 (2)
1.5 (2)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.2 (1.5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.75 (1)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.37 (0.5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
2.2 (3)
2.2 (3)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.5 (2)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
Not
Recommended
0.75 (1)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
Recommended
0.37 (0.5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
3.7 (5)
3.7 (5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
2.2 (3)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
1.5 (2)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.75 (1)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
0.37 (0.5)
NR
NR
15.2
(50)
NR
182.9
(600)
335.3
(1100)
NR
61.0
(200)
182.9
(600)
B
5.5-15
(7.5-20)
5.5-15
(7.5-20)
NR
9.1
(30)
15.2
(50)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
30.5
(100)
91.4
(300)
182.9
(600)
C
18.5-45
(25-60)
18.5-45
(25-60)
NR
9.1
(30)
12.2
(40)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
30.5
(100)
91.4
(300)
182.9
(600)
D
56-93
(75-125)
56-93
(75-125)
NR
9.1
(30)
33.5
(110)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
61.0
(200)
91.4
(300)
182.9
(600)
E
112-224
(150-X300)
112-224
(150-X300)
NR
9.1
(30)
21.3
(70)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
F
187-336
(250-450)
187-336
(250-450)
NR
9.1
(30)
41.1
(135)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
G
224-448
(300-600)
224-448
(300-600)
NR
9.1
(30)
41.1
(135)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
H
522-597
(700-800)
522-597
(700-800)
NR
9.1
(30)
41.1
(135)
91.4
(300)
182.9
(600)
182.9
(600)
NR
61.0
(200)
182.9
(600)
182.9
(600)
182.9
(600)
182.9
(600)
NR = Not Recommended
1
Values shown are for 480V nominal input voltage and drive carrier frequency of 2 kHz. Consult factory regarding operation at carrier frequencies above 2 kHz. Multiply
values by 0.85 for high line conditions. For input voltages of 380, 400 or 415V AC, multiply the table values by 1.25, 1.20 or 1.15, respectively.
2
A 3% reactor reduces motor and cable stress but may cause a degradation of motor waveform quality. Reactors must have a turn–turn insulation rating of 2100 volts or
higher.
3
Includes wire in conduit.
4
Values shown are for nominal input voltage and drive carrier frequency of 2 kHz. Consult factory regarding operation at carrier frequencies above 2 kHz. Multiply values
by 0.85 for high line conditions.
5
Information not available at time of printing.
6
1329R only.