Introduction
1–4
Environmental Specifications
The following environmental guidelines apply to both the 1336 FORCE
Drive and all devices and accessories connected to the Drive.
•
Ambient Operating Temperature:
IP00, Open: 0 to 50 degrees C (32 to 122 degrees F).
IP20, NEMA Type 1 Enclosed:
0 to 40 degrees C (32 to 104 degrees F).
IP65, NEMA Type 4 Enclosed:
0 to 40 degrees C (32 to 104 degrees F).
•
Storage Temperature (all constructions):
–40 to 70 degrees C (–40 to 158 degrees F).
•
Relative Humidity: 5 – 95% non–condensing
•
Altitude: 1000m (3300 ft) without derating.
•
Shock: 15g peak for 11ms duration (+ 1.0 ms).
•
Vibration: 0.006 inches (0.152 mm) displacement. 1G peak.
Electrical Specifications
•
Input Voltage Rating:
200 – 240VAC, Standalone, 3 Phase, +10%, –15% nominal
380 – 480VAC, Standalone, 3 Phase, +10%, –15% nominal
500 – 600VAC Standalone, 3 Phase, +10%, –15% nominal
513 – 621 VDC, Common Bus, +10%, –15% nominal
776 VDC, Common Bus, +10%, –15% nominal
•
Input Power Rating:
2
– 134 KVA (230V)
2 – 437 KVA (380V)
2 – 555 KVA (460V)
2/3 – 578/694 KVA (500/600V)
•
Input Frequency: 50/60HZ (
±
3HZ)
•
Standard Output Voltage*: Four frame sizes are available. Each
frame size is line dependent and can power a motor between the
following voltages:
200 – 240 Vac (line dependent)
380 – 480 Vac (line dependent)
500 – 600 Vac (line dependent)
*If voltage required for your application is not shown, contact
Allen–Bradley for specific application.
•
Output Current: 2.5 – 673A
•
Output Power: 2 – 116 KVA (230V)
2 – 190 KVA (380V)
2 – 208 KVA (415V)
2 – 537 KVA (460V)
2 – 671 KVA (575V)
Note: For information on factors that could effect the power output
of the drive please refer to the Enclosure and Derating Guidelines in
the Appendix of this manual.
•
Output Horsepower (Continuous):
7.5 – 650HP
•
Overload Capability:
Continuous – 100% Fundamental current
1 minute – 150%