Chapter 5
Programming Parameters

5–49

Preset Speed 4
[Preset Speed 4]

Parameter Number

122

Parameter Type

Sink

Display Units

+/– x.x rpm

Drive Units

4096 = Base Motor Speed

Factory Default

+0.0 rpm

Minimum Value

–8 x Base Speed

Maximum Value

+8 x Base Speed

This will be the velocity reference used by
the Drive when preset 4 has been selected
in the Logic Command (P52).

Preset Speed 5
[Preset Speed 5]

This will be the velocity reference used by
the Drive when preset 5 has been selected
in Logic Command (P52).

Parameter Number

123

Parameter Type

Sink

Display Units

+/– x.x rpm

Drive Units

4096 = Base Motor Speed

Factory Default

+0.0 rpm

Minimum Value

–8 x Base Speed

Maximum Value

+8 x Base Speed

Reverse Motor Speed Limit
[Rev Speed Limit]

Parameter Number

127

Parameter Type

Sink

Display Units

– x.x rpm

Drive Units

– 4096 @ Base Motor Speed

Factory Default

– Base Motor Speed

Minimum Value

– 8 x Base Motor Speed

Maximum Value

+ 0.0 rpm

This parameter sets a limit on velocity in
the negative direction. The value entered
must be Negative or Zero. The numeric
range of this parameter is 0 to – 6 times
base motor speed.

Accel Time
[Accel Time]

Parameter Number

125

Parameter Type

Sink

Display Units

x.x Sec

Drive Units

display units x 10

Factory Default

10.0 seconds

Minimum Value

0.0 seconds

Maximum Value

6,553.5 seconds

This parameter displays the ramp rate time
for the velocity reference ramp. Time is
seconds from zero to base motor speed.
Zero will disable accel ramp. See Param
389 & 390 to set this rate.
Note: This parameter not used with a
Standard Adapter Board Equipped Drive.

Decel Time
[Decel Time]

Parameter Number

126

Parameter Type

Sink

Display Units

x.x Sec

Drive Units

display units x 10

Factory Default

10.0 seconds

Minimum Value

0.0 seconds

Maximum Value

6,553.5 seconds

This parameter displays the deceleration
ramp time. Similar to the parameter
above, zero will disable the decel ramp.
See param 391 & 392 to set this rate.
Note: This parameter not used with a
Standard Adapter Board Equipped Drive.

Forward Motor Speed Limit
[Fwd Speed Limit]

Parameter Number

128

Parameter Type

Sink

Display Units

x.x rpm

Drive Units

+ 4096 @ Base Motor Speed

Factory Default

Base Motor Speed

Minimum Value

+ 0.0 rpm

Maximum Value

8 x Base Motor Speed

This parameter sets a limit on velocity in
the positive direction. The value entered
must be Positive or Zero. The numeric
range of this parameter is +6 x base speed
rpm.

Maximum Reverse Speed Trim
[Max Rev Spd Trim]

Parameter Number

129

Parameter Type

Sink

Display Units

+/– x.x rpm

Drive Units

–4096 = Base Motor Speed

Factory Default

– Base Speed

Minimum Value

– 6 x Base Speed

Maximum Value

+ 6 x Base Speed

This parameter limits the minimum value of
the velocity reference after the process trim
output and the external velocity trim has
been added.