Chapter 5
Programming Parameters

5–63

Ki – Regulator
[Ki Flux]

Parameter Number

252

Parameter Type

Sink

Display Units

x

Drive Units

None

Factory Default

125

Minimum Value

0

Maximum Value

32767

Integral gain of the slip regulator This pa-
rameter MUST NOT BE CHANGED.
Data represented as x.

Autotune/Diagnostics Selection
[Autotun Diag Sel]

Parameter Number

256

Parameter Type

Sink

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

0000 0001 1111 1111

Enums:

This parameter allows selection of drive
diagnostic and commisioning tests by set-
ting individual bits in this parameter:

Bit 0 = Inverter transistor Diagnostics
Bit 1 = Motor Phase Rotation Test
Bit 2 = Lsigma Measure Test
Bit 3 = Rs Measure Test
Bit 4 = Id Measure Test
Bit 5 = Torque Block Calc Test
Bit 6 = Motor Inertia Test
Bit 7 = System Inertia Test
Bit 8 = Velocity Loop Gain

Transistor Diagnostics Configuration
[Tran Diag Disabl]

Parameter Number

257

Parameter Type

Sink

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Enums:

This parameter provides a means of disab-
ling certain transistor diagnostic tests by
setting the following bits:

Bit 9 = Disable Power Trans V Lower, for all tests
Bit 10 = Disable Power Trans W Upper, for all tests
Bit 11 = Disable Power Trans W Lower, for all tests
Bit 12 = High Induct*
Bit 13 = Reserved (Always leave 0)
Bit 14 = Reserved (Always leave 0)
Bit 15 = Reserved (Always leave 0)
*

High Inductance motors may need extended test time to de-

termine opens. Setting bit 12 increases the test time.

Inverter Diagnostics Result #1
[Inverter Diag 1]

Parameter Number

258

Parameter Type

Source

Display Units

Bits

Drive Units

None

Factory Default

0000 0000 0000 0000

Minimum Value

0000 0000 0000 0000

Maximum Value

1111 1111 1111 1111

Enums:

The results of the Transistor Diagnostic
Tests are given in parameter 258 &
259.

Bit 0 = Software Fault
Bit 1 = No motor connected, or open bus fuse
Bit 2 = Phase U and W Shorted
Bit 3 = Phase U and V shorted
Bit 4 = Phase V and W shorted
Bit 5 = Shorted modules
Bit 6 = Ground fault
Bit 7 = Fault before shorted module ran
Bit 8 = Hardware overvoltage fault occurred

Bit 9 = Hardware desaturation fault occurred
Bit 10 = Hardware ground fault occurred
Bit 11 = Hardware phase overcurrent fault occurred
Bit 12 = Open power transistor(s)

See bit 12 in parameter 257

Bit 13 = Current feedback fault(s)
Bit 14 = Reserved. Leave Zero
Bit 15 = Reserved, Leave Zero

Bit 0 = Disable I feedback phase U offset
Bit 1 = Disable I feedback phase W offset
Bit 2 = Disable Shorted Transistor Tests
Bit 3 = Disable Ground Fault Tests
Bit 4 = Disable Open device tests
Bit 5 = Not Used
Bit 6 = Disable Power Trans U Upper, for all tests
Bit 7 = Disable Power Trans U Lower, for all tests
Bit 8 = Disable Power Trans V Upper, for all tests